Basic
Testing of DSC Panels
PC585, PC1565, Power 608, Power 832
1) Connect a keypad to the panel
2) Connect a 1K OHM (Brown-Black-Red) across the Bell terminals
3) Connect the battery to the battery red & black leads.
4) Connect the telephone line to the Ring & Tip terminals
5) Default the panel to factory settings by wiring a short between PGM1 and zone input 1
and then applying 16.5VAC power (plug pack) to the AC input terminals
6) After approximately 4 seconds the keypad will produce a number of “beeps” indicating
that the unit has reset to factory settings.
If installer lockout has been enabled the unit’s line relay will quickly click 10 times
indicating that the panel can not be reset to factory settings. You will need the installer
code to reset the panel.
If the early model Power 832 (version 1.0 software) is defaulted to factory settings it
will return to North American settings (ie no reporting codes, 4+2 format, etc.). The
unit will need to be re-programmed to Australian requirements, either via a download
or manually by the keypad
7) Remove the short between PGM1 and zone 1.
8) The trouble (or System) LED will be illuminated because there is no time or date in the
panel. Enter [*6] Master Code [1234] then [1] for time and date. You can now just exit
out by pressing [#] and there should now be no troubles in the system.
9) Enter the Programming – [*8] [Installer code].
a) For convenience of testing, program the system times to shorter intervals, enter [005]
(entry delay time) and then [005] (exit delay time) and then press [#].
b) If the unit is a PC585, PC1565 or Power608 program the units PGM1 to be a strobe
output (type [10] in location [009]).
C)
Enter the monitoring station receiver telephone number in location [301]
d) Enter the 4 digit central station account number in location [310] (any 0 is entered as
an A [*1 *]). Escape out of programming mode [#].
10) If the trouble (or System) LED is illuminated press [*2] to ascertain the trouble. The
troubles are described in the Keypad Commands section of the installation manual.
11) Test that the Auxiliary DC output voltage is correct by placing a meter set to 20volts
DC across the AUX + and – terminals (Red to + and Black to -). The meter should read
between 13.7 and 13.85 volts DCI
If the AUX voltage is either to high or to low then the panel should be sent to DSC
for repair.
Vedere la pagina 0
1 2 3

Sommario

Pagina 1 - Testing of DSC Panels

1Phone (02) 9564 5812 or 1800 252 960 Basic Testing of DSC Panels PC585, PC1565, Power 608, Power 832 1) Connect a keypad to the panel 2) Co

Pagina 2

212) To check to see if the zones are operating OK place a 5.6K Ohm resistor (Green-Blue-Red) across zone 1 input to a COM and the zone 1 LED should

Pagina 3

318) With the Armed light illuminated remove one leg of the resistor installed between zone 1 and COM. The entry warning tone will be generated by th