P R O G R A M D E S C R I P T I O N S
27
5.7.6 Priority/Emergency
The panel will transmit a Keypad Fire Alarm Reporting Code AND the Keypad Fire Restoral Reporting
Code when the Fire Keys on any keypad is pressed for two seconds.
The panel will transmit a Keypad Auxiliary Alarm Reporting Code AND the Keypad Auxiliary Restoral
Reporting Code when the Auxiliary Keys on any keypad is pressed for two seconds.
The panel will transmit a Keypad Panic Alarm Reporting Code AND the Keypad Panic Restoral
Reporting Code when the Panic Keys on any keypad is pressed for two seconds.
The panel will transmit a Duress Reporting Code any time either Duress Code is entered at any keypad. If
the panel is armed using the Duress Code the panel will also transmit a Closing by Duress Reporting
Code or if the panel is disarmed it will also transmit an Opening by Duress Reporting Code.
5.7.7 Maintenance
The panel will transmit a Battery Trouble Alarm Reporting Code when the backup battery drops below
11.5 V
DC. The Battery Trouble Restoral Reporting Code will not be transmitted until the battery has been
charged over 12.5 V
DC.
To prevent the panel from transmitting an AC Failure Trouble Alarm Reporting Code during short power
outages the panel will not send the signal unless AC power is lost for the amount of minutes programmed
for the AC Failure Communication Delay. The AC Failure Trouble Restoral Reporting Code will be
transmitted as soon as AC power is restored.
A Bell Circuit Trouble Alarm Reporting Code will be transmitted immediately if an open condition is
measured on the Bell Output of the main panel. The Bell Circuit Trouble Restoral Reporting Code will be
transmitted as soon as the problem is corrected.
A Fire Trouble Alarm Reporting Code will be transmitted immediately when an open condition is
measured on any Fire type zone
(See Section 5.1 “Zone Definitions”).
The Fire Trouble Restoral
Reporting Code will be transmitted as soon as the problem is corrected.
The Auxiliary Power Supply Trouble Alarm Reporting Code will be transmitted if the AUX output is
shorted. The AUX output control incorporates a fuseless design. When excessive current is drawn the
panel will automatically shut off the output. The panel will constantly check the AUX output and when the
excessive current draw is removed the panel will reset the output and transmit an Auxiliary Power Supply
Trouble Restoral Reporting Code.
The TLM Restoral Reporting Code will be transmitted within 10 seconds of a telephone line monitoring
problem being corrected.
A General System Trouble Reporting Code will be transmitted if the panel detects any of the following on
the PC5204 Power Supply/Output Module: AC Power Failure, Low Battery, AUX Output Trouble, Output #1
Supervisory trouble or the PC5400 is off-line. The General System Trouble Restoral Reporting Code will
be transmitted when all of the listed problems are corrected.
A General System Supervisory Trouble Reporting Code will be transmitted if any module goes missing
from the Keybus. If the module is a zone expander the panel will also transmit the Zone Expander
Supervisory Alarm Trouble Reporting Code. The panel will send a General System Supervisory
Restoral Reporting Code when the problem is corrected as well as a Zone Expander Supervisory
Restoral Reporting Code if the module is a zone expander.
5.7.8 Test Transmissions
The panel can be programmed to transmit a Periodic Test Transmission
Reporting Code
(See Section
5.13 “Test Transmissions”)
or a System Test Reporting Code
(See Section 3.4 “[ ] Commands, [ ] [6]”).
5.7.9 Miscellaneous
The panel will transmit the Keypad Lockout Reporting Code if the lockout is activated
(See Section 5.22
“Keypad Lockout”)
.
The DLS Lead In Reporting Code will only be transmitted if the DLS Call Back feature is being used
(See
Section 5.8 “Downloading”)
. Before the panel calls the computer back it will call central station and
transmit the reporting code to indicate a download session is about to begin. After downloading is
complete the panel will transmit a DLS Lead Out Reporting Code to indicate the download session is
complete.
If the panel fails to transmit information to the central station it will display a failure to communicate trouble
condition. The panel will transmit a Phone Number 1 Failure to Communicate Reporting Code or a
Phone Number 2 Failure to Communicate Reporting Code the next time it calls the central station. The
panel will transmit the old events, followed by the failure to communicate, followed by the new events. This
will allow central station to determine which events are old or new.
If the Event Buffer is uploaded on a regular basis an Event Buffer 75% Full Reporting Code can be
transmitted to warn the Buffer is almost full. This is also useful if the PC5400 Printer Module is being used.
Reporting Codes........................................................................... Section [320] to [353]